Tripping circuit breaker W6E
\uD83E\uDD14 Tripping circuit breaker when W6E is turned on or off
The regular circuit breaker (30mA) could trip when the roaster is turned on or off. This has to do with leakage voltage, which could be caused by all other devices, this has nothing to do with the roaster itself. As our roasters meet the IEC-NEN 60201-1 standard, below solution can be used.
\uD83C\uDF31 Solution
Create a separate circuit which must have its own type B or F earth leakage circuit breaker and be greater than 30mA. Giesen can’t say how much the circuit breaker must be, cause all depends on how much leakage voltage is present.
Filter by label
There are no items with the selected labels at this time.